Control circuit specifications Wiring
3 - 22
Using an external power supply
Sink logic type
Use terminal PC as a common terminal to prevent a malfunction caused by undesirable
current. (Do not connect terminal SD of the inverter with terminal 0V of the external power
supply. When using terminals PC-SD as a 24V DC power supply, do not install a power
supply in parallel in the outside of the inverter. Doing so may cause a malfunction due to
undesirable current.)
Source logic type
When using an external power supply for transistor output, use terminal SD as a common
to prevent misoperation caused by undesirable current.
Fig. 3-12:
Using an external power supply in connection
with the outputs of a PLC
I001030E
Fig. 3-13:
Using an external power supply in connection
with the outputs of a PLC
I001031E
AY40 Inverter
Current
AY80 Inverter
Current