Basic settings PU operation mode
FR-E700 EC 5 - 23
5.2.2 Use the digital dial like a potentiometer to perform operation
● Set "1" (setting dial potentiometer mode) in Pr. 161 "Frequency setting/key lock operation
selection".
쑶
Example 쑴 Change the frequency from 0Hz to 50Hz during operation.
I001768E
Fig. 5-13: Use the digital dial like a potentiometer to perform operation
NOTES
If flickering "50.00" turns to "0.0", the Pr. 161 "Frequency setting/key lock operation selec-
tion" setting may not be "1".
Independently of whether the inverter is running or at a stop, the frequency can be set by
merely turning the digital dial.
Use Pr. 295 "Magnitude of frequency change setting" to change the frequency setting incre-
ments of the digital dial.
Screen at powering on
The monitor display appears.
Press the PU/EXT key to choose the PU
operation mode.
Chage the PR. 161 setting to "1".
(Refer to page 4-15.)
Press the RUN key to start the inverter.
Turn the digital dial until "50.00" appears.
The flickering frequency is the set frequency.
You don’t need to press the SET key.
Operation Display
PU indication is lit.
The frequency flickers for about 5s