Limit the output frequency Parameter
6 - 52
6.4.2 Avoid mechanical resonance points (frequency jumps) (Pr. 31 to Pr. 36)
When it is desired to avoid resonance attributable to the natural frequency of a mechanical sys-
tem, these parameters allow resonant frequencies to be jumped.
The above parameters can be set when Pr. 160 "User group read selection" = 0.
Up to three areas may be set, with the jump frequencies set to either the top or bottom point of
each area.
The settings of frequency jumps 1A, 2A, 3A are jump points, and operation is performed at these
frequencies in the jump areas.
Pr.
No.
Name Initial Value Setting Range Description Parameters referred to
Refer to
Section
31
Frequency jump 1A 9999 0–400Hz/9999
1A to 1B, 2A to 2B, 3A to 3B is
frequency jumps
9999: Function invalid
32
Frequency jump 1B 9999 0–400Hz/9999
33
Frequency jump 2A 9999 0–400Hz/9999
34
Frequency jump 2B 9999 0–400Hz/9999
35
Frequency jump 3A 9999 0–400Hz/9999
36
Frequency jump 3B 9999 0–400Hz/9999
Fig. 6-11:
Definition of the jump areas
I000019C
Hz
Pr.36 (3B)
Pr.35 (3A)
Pr.34 (2B)
Pr.33 (2A)
Pr.32 (1B)
Pr.31 (1A)
Set frequency
Output frequency