Function assignment of external terminals Parameter
6 - 134
When you refer to Fig. 6-65 and set "1" to the terminal bit (terminal where the REM signal has
been assigned) of Pr. 496 or Pr. 497, the output terminal turns on (off for sink logic). By setting
"0", the output terminal turns off (on for sink logic).
As desired (always "0" when read).
Y0 to Y6 are available only when the extension output option (FR-A7AY E kit) is fitted.
RA1 to RA3 are available only when the relay output option (FR-A7AR E kit) is fitted.
Example When "96" (source logic) is set to Pr. 190 "RUN terminal function selection" and "1" (H01) is
set to Pr. 496, the terminal RUN turns on.
I001799E
Fig. 6-65: Remote output data
Pr. 496
Pr. 497