Parameter Limit the output frequency
FR-E700 EC 6 - 53
The following diagrams show how the jump point is selected. The diagram on the left shows a
sequence in which the jump takes place at the end of the area to be jumped, for which the lower
frequency must be entered first. In the diagram on the right the jump takes place at the beginning
of the frequency area to be jumped, for which the higher frequency must be entered first.
I00019aC
Fig. 6-12: Selection of the jump point
NOTE During acceleration/deceleration, the running frequency within the set area is valid.
Hz Hz
Pr.32 (1B)
Pr.31 (1A)
Pr.31 (1A)
Pr.32 (1B)
32 32
38 38
Set frequency
Set frequency
Output frequency