Job Name: Location: Date:
Purchaser: Engineer:
Submitted to: For Reference Approval Construction
Unit Designation: Schedule No.:
GENERAL FEATURES
• Compact side discharge
outdoor unit
• Wireless or wired remote
controller, depending on the
indoor units used
• Quiet operation—both indoor
and outdoor units
• Automatic fan speed control
• Auto restart following a power
outage
• Self-check function—integrated
diagnostics
• Advanced microprocessor control
• Limited warranty: one year on parts and
defects and six years on compressor
OPTIONAL OUTDOOR UNIT ACCESSORY
• Air Outlet Guide (MAC-855SG)
Cooling*
Rated Capacity (Non-ducted/Ducted) ...28,400 Btu/h / 27,400 Btu/h
Minimum Capacity (Non-ducted/Ducted)
. .12,600 Btu/h / 12,600 Btu/h
Total Input (Non-ducted/Ducted)
..............3,250 W / 3,300 W
Heating at 47°F*
Rated Capacity (Non-ducted/Ducted)
...28,600 Btu/h / 27,600 Btu/h
Minimum Capacity (Non-ducted/Ducted)
. . 11,400 Btu/h / 11,400 Btu/h
Total Input (Non-ducted/Ducted)
..............2,180 W / 2,220 W
Heating at 17°F*
Rated Capacity (Non-ducted/Ducted)
...16,000 Btu/h / 15,100 Btu/h
Total Input (Non-ducted/Ducted)
..............1,690 W / 1,590 W
* Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB / 67ºF (19ºC) WB.
Outdoor: 95ºF (35ºC) DB / 75ºF (24ºC) WB.
(Heating) - Indoor: 70ºF (21ºC) DB / 60ºF (16ºC) WB. Outdoor: 47ºF (8ºC) DB /
43ºF (6ºC) WB.
(Heating at 17ºF) - Indoor: 70ºF (21ºC) DB / 60ºF (16ºC) WB. Outdoor: 17ºF
(-8ºC) DB / 15ºF (-9ºC) WB.
Power Supply
....................208 / 230V, 1-Phase, 60 Hz
Breaker Size
........................................20 A
MCA
............................................ . 15 A
Voltage
Indoor - Outdoor S1-S2
......................AC 208 / 230V
Indoor - Outdoor S2-S3
........................DC 12 - 24V
OPERATING RANGE
Indoor Intake Air Temp. Outdoor Intake Air Temp.
Cooling
Maximum 95ºF (35ºC) DB, 71ºF (22ºC) WB 115ºF (46ºC) DB
Minimum 67ºF (19ºC) DB, 57ºF (14ºC) WB 14ºF (-10ºC) DB
Heating
Maximum 80ºF (27ºC) DB, 67ºF (19ºC) WB 75ºF (24ºC) DB, 65ºF (18ºC) WB
Minimum 70ºF (21ºC) DB, 60ºF (16ºC) WB 14ºF (-10ºC) DB, 12ºF (-11ºC) WB
Compressor ..................DC Inverter-driven Twin Rotary
Fan Motor
....................................0.93 F.L.A.
Sound Pressure Level
Cooling
...................................... . . 49 dB(A)
Heating
....................................... . 49 dB(A)
W 35-7/16 / 900
D 12-5/8 / 320
H 35-7/16 / 900
Weight ...................................148 lbs. / 67 kg
Refrigerant Type
.................................. R410A
Refrigerant Pipe Size O.D. ― Three Ports
Gas Side
...............A: 1/2 / 12.7 mm; B, C: 3/8" / 9.52 mm
Liquid Side
................................1/4" / 6.35 mm
Max. Refrigerant Pipe Length
.....................230' / 70 m
Max. Refrigerant Pipe Height Difference
If Indoor Unit is Above Outdoor Unit
............... 49' / 15 m
If Indoor Unit is Below Outdoor Unit
................ 33' / 10 m
Connection Method
................................Flared
Remote Controller PAR-21MAA -
Packaged with SEZ
Outdoor Unit: MXZ-3A30NA
Wireless Remote Controller -
Packaged with MSZ-A and MSZ-FD
(Optional Wired PAR-21MAA Remote
Controller)
Indoor Unit Type SEER HSPF
16 10
15.2 9.7
14.5 9.5
Outdoor Unit ................................MXZ-3A30NA
Indoor Unit
.....Two (minimum) or Three Indoor Units Necessary
(Select Style as Installation Requires)