3-2.Function list
The use of GB-50A requires a license registration. By registering the license, group or block operation of
the units on the Web browser will become available. Registration for the license that is required to use
various functions can be completed on the license registration page.
Table 3-2 List of Web monitoring function
Item Content
Start/stop Switching start/stop collectively or for each group
Operation mode Switching cool/dry/fan/auto/heat collectively or for each group
Temperature setting Setting room temperature collectively or for each group
Set temperature range Cool/dry: 19ºC-30ºC /67ºF-87ºF
Heat: 17ºC-28ºC /63ºF-83ºF
Auto: 19ºC-28ºC /67ºF-83ºF
*Note: Preset temperature range varies on different models.
Air velocity Switching air velocity in 4 steps collectively or for each group.
Air direction Switching in 4 steps vertically and for swing collectively or for each group
(Selectable air direction differs depending on the model)
Start/stop of interlocked
equipment (Lossnay)
Switching start (Hi/Lo)/stop collectively or for each group when connecting with
interlocked equipment (Lossnay).
(However, ventilation mode can not be selected for the interlocked equipment.)
Prohibition of local control Selecting the items for which local control is prohibited collectively or for each
group.
(Items include start/stop, operation mode, temperature setting and filter sign.)
Error display Identifies the unit in trouble and displays the nature of trouble
Filter sign display and
reset
Filter sign display can be reset in each group or collectively.
Malfunction history Malfunction history can be check up to 64 contents in both unit and
communication error.
Annual/weekly schedule Using the annual/weekly schedule function by license registration.
Malfunction e-mail history E-mail history can be check up to 64 contents.
* The above specification may be changed depending on the equipment connected or combined.
* The block setting and the registration of block/group names require the initial setting tool or initial setting
web.
*Without prior notice, the content may be changed.