2. External signal output function
* External signal output requires the external I/O adapter (Model: PAC-YG10HA) sold separately.
(1) External output
When one or more air conditioners are running, the “ON” signal will be output and if a malfunction occurs
in one or more air conditioners, the “Malfunction” signal will be shown.
(2) External output specifications
1 “ON” signal and “Malfunction”
signal will both be shown.
(3) Recommended circuit example
Use Z1 and Z2 relays having the following specifications.
Operation coil
Rated voltage : DC12V, DC24V
Power consumption : 09.W or less
(*1) Prepare a power supply separately according to the relay
being used. (DC12V or DC24V)
(*2) Always insert a diode on both ends the relay coil.
1 Each element will turn on while ON operation or a malfunction occurs.
2 The connection cable can be extended up to 10m (32 ft).
3 The relays, lamps, diodes and extension cables, etc, must be prepared separately at the site.
CN2 Lead wire Details of each terminal
No.1 Green Common (External ground)
No.2 Black ON/OFF
No.3 Brown Malfunction/normal
No.9 Red Common (External power supply) (*1)