Mitsubishi Electric Central Controller GB-50A Manuel d'installation Page 1

Naviguer en ligne ou télécharger Manuel d'installation pour Matériel d'enregistrement Mitsubishi Electric Central Controller GB-50A. Mitsubishi Electric Central Controller GB-50A Installation manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 20
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Mitsubishi Electric Air-conditioner Network System
Central Controller
Model: GB-50A
Installation Manual
Contents
Before using the controller, please read this Installation Manual carefully to ensure correct
operation. Store this Installation Manual in a location that is easy to find.
1. Safety Precautions to be Observed without Fail ..........1
2. Confirmation of Parts .................................................3
3. Product Feature.........................................................4
4. System Diagram ........................................................5
5. Installation Method ....................................................7
1. Part prepared at site ..............................................7
2. Allowable length of M-NET transmission lines.........7
3. Installation method ................................................8
6. Wiring Method .........................................................11
1. Grounding cable. .................................................11
2. Cover removal and installation .............................11
3. M-NET transmission line ......................................12
4. LAN connection ...................................................12
7. Initial setting............................................................13
1. How to set the IP address with dip switches .........14
2. Setting of the service switch.................................14
8. Test Run .................................................................15
1. Collective operation ON/OFF ...............................15
2. Service LED display.............................................15
9. Example for System Configuration............................16
1. To control a K control model ................................16
2. To use system controllers on multiple units ..........16
10. External Input/Output Usage Method ......................16
1. External signal input function ...............................16
2. External signal output function .............................18
Vue de la page 0
1 2 3 4 5 6 ... 19 20

Résumé du contenu

Page 1 - Installation Manual

Mitsubishi Electric Air-conditioner Network System Central Controller Model: GB-50A Installation Manual Contents

Page 2

9 Method2: Vertical installation using L-fittings After removing the screws on GB-50A, attach two L-fittings to GB-50A using the supplied screws (Fi

Page 3

10 Fig.5-6 unit:mm(in) Installation and de-installation on DIN rail 1) Installation Put the upper side of attachment on DIN rai

Page 4 - 2 Confirmation of Parts

11 1. Grounding cable Connect the protective earth cable (grounding cable) to the ground terminal as shown in the Fig.6-1. Attach the rin

Page 5 - 3 Product Feature

12 4. LAN connection M-NET transmission A, B line (Non-polarity DC24V) M-NET M-NET transmission A, B line (Non-polarity DC24V)

Page 6 - 4 System Diagram

13 Initial setting steps Step 1: IP address setting Step 2: License number registration *License must be r

Page 7 - Control area of sub SC

14 1. How to set the IP address with dip switches IP addresses between 192.168.1.1 and15 can be set using the 4-pin dip switch on SW2. Set this switc

Page 8 - 5 Installation Method

15 1. Collective operation ON/OFF * After setting the group or interlocked setting, confirm that the controller has started up, and then perform a

Page 9

16 1. To control a K control model ● Set GB-50A address to “000” when a K transmission Converter is connected. Always set to the master system Cont

Page 10 - Fig.5-4 unit:mm(in)

17 (2) Level signal and pulse signal (DC12V or DC24V) (3) External input specification CN2 Lead wire Emergency stop/normal level sign

Page 11

18 2. External signal output function * External signal output requires the external I/O adapter (Model: PAC-YG10HA) sold separately. (1) External o

Page 12 - 6 Wiring Method

1 This manual describes the installation of the central controller and wiring to the air conditioner. Refer to the installation manual of the air co

Page 14 - 7 Initial Setting

2 CAUTION Do not touch the PCB (Printed CircuitBoard) with your hand or a tool. Also donot get dirt on the PCB. It may cause

Page 15

3 *Please confirm that in addition to this Installation Manual the following items are enclosed in the box. No. Part name Qty. 1 Central controlle

Page 16 - 8 Test Run

4 1. Specification Item Contents Interface M-NET :DC30V/24V;0.13/0.15A External I/O :DC12V or 24V (External power supply) Ethernet :

Page 17

5 Address setting method Address Indoor unit Set the indoor unit you want to make them master unit in the same group to t

Page 18

6 NOTE * This system controller is designed as a main controller, not as a sub controller. ● Main system controller (main SC) The main

Page 19 - No.2 Black ON/OFF

7 1. Parts prepared at site Please prepare the following parts before installation of the unit. Preparation parts Specification Unit fixing screw

Page 20

8 1) Maximum length of M-NET transmission 1 L2+L3+L4+ℓ1+ℓ2+ℓ3 (ℓ4) =500m/1640 ft 2 L2+L3+L4+ℓ1+ℓ5 =500m/1640 ft 3 L2+L3+L5+ℓ6+ℓ7 (ℓ8) =500m/1640 f

Commentaires sur ces manuels

Pas de commentaire