WY-SERIES SYSTEM DESIGN (June 2010)
WYSD-1
WY-SERIES
SYSTEM DESIGN
CITY MULTI
®
WY-SERIES
SYSTEM DESIGN
1. ELECTRICAL WORK ........................................................................................................................................... WYSD-2
1-1. General Cautions .......................................................................................................................................WYSD-2
1-2. Power Supply for Indoor Unit and Water-source Unit ................................................................................WYSD-3
1-3. PowerCableSpecications .......................................................................................................................WYSD-6
1-4. Power Supply Examples ............................................................................................................................WYSD-7
2. M-NET CONTROL..............................................................................................................................................WYSD-10
2-1. Transmission Cable Length Limitation .....................................................................................................WYSD-10
2-2. TransmissionCableSpecications .......................................................................................................... WYSD-11
2-3. SystemCongurationRestrictions ........................................................................................................... WYSD-12
2-4. Address Setting ........................................................................................................................................WYSD-15
3. PIPING DESIGN ................................................................................................................................................WYSD-25
3-1. R410A Piping Material ..............................................................................................................................WYSD-25
3-2. PQHY-P-T/Y(S)HMU’s Piping Design ......................................................................................................WYSD-26
3-3. Refrigerant CHarging Calculation ............................................................................................................WYSD-30
4. INSTALLATION ..................................................................................................................................................WYSD-31
4-1. PQHY-P-T/Y(S)HMU’s Installation ...........................................................................................................WYSD-31
4-2. Installation Space .....................................................................................................................................WYSD-31
4-3. Piping Direction ........................................................................................................................................ WYSD-32
5. CAUTIONS .........................................................................................................................................................WYSD-33
5-1. Refrigerant Properties .............................................................................................................................. WYSD-33
5-2. ConrmtheCriticalConcentrationandPerformCountermeasures .........................................................WYSD-33
Vue de la page 0
1 2 3 4 5 6 ... 33 34

Résumé du contenu

Page 1 - SYSTEM DESIGN

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-1WY-SERIES SYSTEM DESIGNCITY MULTI® WY-SERIES SYSTEM DESIGN1. ELECTRICAL WORK ...

Page 2 - 1-1. General Cautions

WYSD-10WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN2. M-NET CONTROL2-1. Transmission Cable Length Limitation *1. If the length from ME t

Page 3

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-11WY-SERIES SYSTEM DESIGN2. M-NET CONTROL2-2. Transmission Cable SpecicationsType of cableCable sizeRemarksSh

Page 4

WYSD-12WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN2. M-NET CONTROL2-3. System Conguration RestrictionsME remote controllerME remote co

Page 5

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-13WY-SERIES SYSTEM DESIGN2. M-NET CONTROLHeat source unitHeat source unitHeat source unitHeat source unitMA re

Page 6

WYSD-14WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN2. M-NET CONTROL1-phase 208-230V AC power supply is needed.The power supply unit is n

Page 7 - 1-4. Power Supply Examples

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-15WY-SERIES SYSTEM DESIGN2. M-NET CONTROL2-4. Address Setting1234ON1234ONBranchNo. settingUnit address No. set

Page 8 - Breakers for current leakage

WYSD-16WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN2. M-NET CONTROL2-4-2. Rule of setting addressUnitIndoor unit,Lossnay,PAC-YG63MCA(AI

Page 9

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-17WY-SERIES SYSTEM DESIGN2. M-NET CONTROL2-4-3. System examplesFactory settingSetting at the siteOriginal swit

Page 10 - 2. M-NET CONTROL

WYSD-18WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN2. M-NET CONTROL2-4-3-2. MA remote controller, Single-refrigerant-system, System Cont

Page 11

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-19WY-SERIES SYSTEM DESIGN2. M-NET CONTROL2-4-3-3. MA remote controller, Multi-refrigerant-system, System Contr

Page 12

WYSD-2WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN1. ELECTRICAL WORK1-1. General CautionsOK NOFollow ordinance of your governmental orga

Page 13

WYSD-20WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN2. M-NET CONTROL2-4-3-4. ME remote controller, Single-refrigerant-system, No system c

Page 14

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-21WY-SERIES SYSTEM DESIGN2. M-NET CONTROL2-4-3-6. ME remote controller, Multi-refrigerant-system, System Contr

Page 15 - 2-4. Address Setting

WYSD-22WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN2. M-NET CONTROLPQHY-P-TSHMU/YSHMU PQHY-P-TSHMU/YSHMU PQHY-P-THMU/YHMUPQHY-P-TSHMU/YS

Page 16

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-23WY-SERIES SYSTEM DESIGN2-4-3-8. LMAPLMAP(01)24VDC(LONWORKS adapter)PCLONWORKS cardLONWORKS cardLONWORKS card

Page 17

WYSD-24WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN2-4-3-9. BM ADAPTERBAC netHeat source unit(PQHY)Heat source unit(PQHY)Heat source uni

Page 18

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-25WY-SERIES SYSTEM DESIGN3. PIPING DESIGN3-1. R410A Piping Material Refrigerant pipe for CITY MULTI shall be m

Page 19

WYSD-26WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN3. PIPING DESIGN3-2. Piping DesignTable3-2-1-6. R410A Joint selection rule Total down

Page 20

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-27WY-SERIES SYSTEM DESIGN3. PIPING DESIGNTable3-2-2-6. R410A Joint selection rule Total down-stream Indoor cap

Page 21

WYSD-28WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN3. PIPING DESIGNTable3-2-3-6. R410A Joint selection rule Total down-stream Indoor cap

Page 22

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-29WY-SERIES SYSTEM DESIGN3. PIPING DESIGN19718016414813111598826698 115 131 148 164 180Farthest Indoor unit fr

Page 23

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-3WY-SERIES SYSTEM DESIGN1. ELECTRICAL WORK1-2. Power Supply for Indoor Unit and Water-source Unit1-2-1. Electr

Page 24

WYSD-30WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN(1) Calculation of additional refrigerant charge Calculate the amount of additiona

Page 25 - 3-1. R410A Piping Material

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-31WY-SERIES SYSTEM DESIGN4-1. PQHY-P-T(S)HMU/Y(S)HMU’s Installation4. INSTALLATION1. Install indoors; avoid e

Page 26 - 3-2. Piping Design

WYSD-32WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN4. INSTALLATION4-3. Piping Direction1. Insulation installation With City Multi WY/ WR

Page 27

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-33WY-SERIES SYSTEM DESIGN5. CAUTIONSR410A refrigerant is harmless and incombustible. The R410A is heavier than

Page 28

WYSD-34WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN

Page 29

WYSD-4WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN1. ELECTRICAL WORKSymbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIF

Page 30

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-5WY-SERIES SYSTEM DESIGN1. ELECTRICAL WORKSymbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIF

Page 31 - 4-2. Installation Space

WYSD-6WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN1. ELECTRICAL WORK1-3. Power Cable SpecicationsThickness of wire for main power suppl

Page 32 - 4-3. Piping Direction

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-7WY-SERIES SYSTEM DESIGN1-4. Power Supply Examples1. ELECTRICAL WORK The local standards and/or regulation

Page 33 - 5-1. Refrigerant Properties

WYSD-8WY-SERIES SYSTEM DESIGN (June 2010)WY-SERIES SYSTEM DESIGN1. ELECTRICAL WORK The local standards and/or regulations is applicable at a highe

Page 34 - WY-SERIES

WY-SERIES SYSTEM DESIGN (June 2010)WYSD-9WY-SERIES SYSTEM DESIGN1. ELECTRICAL WORK The local standards and/or regulations is applicable at a highe