Mitsubishi Electric MSZ-HJ35VA-E1 Manuel de service

Naviguer en ligne ou télécharger Manuel de service pour Climatiseurs à système divisé Mitsubishi Electric MSZ-HJ35VA-E1. Mitsubishi Electric MSZ-HJ35VA-E1 Service manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 48
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 3
3. SPECIFICATION ················································ 4
4. NOISE CRITERIA CURVES ······························ 7
5. OUTLINES AND DIMENSIONS ························ 8
6. WIRING DIAGRAM ············································ 9
7. REFRIGERANT SYSTEM DIAGRAM ··············11
8. PERFORMANCE CURVES ····························· 13
9. ACTUATOR CONTROL ··································· 24
10. SERVICE FUNCTIONS ···································· 25
11. TROUBLESHOOTING ····································· 25
12. DISASSEMBLY INSTRUCTIONS ···················· 42
Models
SPLIT-TYPE AIR CONDITIONERS
MUZ-HJ25VA
-
E1
MUZ-HJ35VA
-
E1
MUZ-HJ50VA
-
E1
HFC
utilized
R410A
No. OBH648
REVISED EDITION-A
OUTDOOR UNIT
Indoor unit service manual
MSZ-HJ•VA Series (OBH647)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
PARTS CATALOG (OBB648)
MUZ-HJ25VA
MUZ-HJ35VA
Revision A:
• MUZ-HJ50VA-
E1
has been added.
Please void OBH648.
Vue de la page 0
1 2 3 4 5 6 ... 47 48

Résumé du contenu

Page 1 - MUZ-HJ50VA

SERVICE MANUALCONTENTS1. TECHNICAL CHANGES ··································· 32. PART NAMES AND FUNCTIONS ····················· 33. SPECIFICATION ··

Page 2 - Revision A:

10MUZ-HJ50VAOBH648A

Page 3 - PART NAMES AND FUNCTIONS

11Unit : mmMUZ-HJ25VA MUZ-HJ35VAMUZ-HJ50VAOutdoorheatexchangerFlared connectionDefrostthermistorRT61DischargetemperaturethermistorRT62Flared connecti

Page 4 - SPECIFICATION

12MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCERefrigerant piping: mPiping size O.D: mmMax. LengthAMax. Height differenceBGas LiquidMUZ-HJ

Page 5

13The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi-tions vary according t

Page 6

14Indoor intake air Dry-bulb temperature (°C)Outdoor intake air Wet-bulb temperature (°C) Outdoor intake air Wet-bulb temperature (°C) Indoor intake a

Page 7 - NOISE CRITERIA CURVES

150 50 1001500.51.01.50 50 1001500.51.01.50 50 1001500.51.01.50 50 1001500.51.01.50 50 1001500.51.01.50 50 1001500.51.01.50 50 1001500.51.01.50 50 100

Page 8 - OUTLINES AND DIMENSIONS

16Outdoor low pressureMUZ-HJ25VAMUZ-HJ35VA MUZ-HJ50VA45678934567823456715 20 25 30 350.40.50.60.70.80.915 20 25 30 350.30.40.50.60.70.815 20 25 30 350

Page 9 - WIRING DIAGRAM

17PERFORMANCE DATA COOL operation at Rated frequencyMUZ-HJ25VACAPACITY: 2.5 kW SHF: 0.89 INPUT: 730 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)21 25

Page 10

18PERFORMANCE DATA COOL operation at Rated frequencyMUZ-HJ25VACAPACITY: 2.5 kW SHF: 0.89 INPUT: 730 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)35 40

Page 11 - REFRIGERANT SYSTEM DIAGRAM

19PERFORMANCE DATA COOL operation at Rated frequencyMUZ-HJ35VACAPACITY: 3.15 kW SHF: 0.87 INPUT: 1040 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)21

Page 12

2<Preparation before the repair service> Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stoppi

Page 13 - PERFORMANCE CURVES8

20PERFORMANCE DATA COOL operation at Rated frequencyMUZ-HJ35VACAPACITY: 3.15 kW SHF: 0.87 INPUT: 1040 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)35

Page 14 - defrost operation

21PERFORMANCE DATA COOL operation at Rated frequencyMUZ-HJ50VACAPACITY: 5.0 kW SHF: 0.70 INPUT: 2050 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)21 2

Page 15

22PERFORMANCE DATA COOL operation at Rated frequencyMUZ-HJ50VACAPACITY: 5.0 kW SHF: 0.70 INPUT: 2050 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)35 4

Page 16 - MUZ-HJ35VA MUZ-HJ50VA

23PERFORMANCE DATA HEAT operation at Rated frequencyMUZ-HJ25VACAPACITY: 3.15 kW INPUT: 870 WINDOORDB (°C)OUTDOOR WB (°C)-10 -5 0 5 10 15 20Q INPUT Q

Page 17

24MUZ-HJ25VA MUZ-HJ35VA MUZ-HJ50VA9-2. R.V. COIL CONTROL R.V. COIL CONTROL MUZ-HJ25VA MUZ-35VAHeating . . . . . . . . . . . . . . . . . OFF Coo

Page 18

2510-1. CHANGE IN DEFROST SETTING <JS> When the JS wire of the inverter P.C. board is cut/ soldered, the defrost finish temperature is changed.

Page 19

26Outline of the functionThis air conditioner can memorize the abnormal condition which has occurred once.Even though LED indication listed on the tro

Page 20

27 2. Flow chart of the detailed outdoor unit failure mode recall function 2.Blinking pattern when outdoor unit is abnormal:ONOFFNo beepBeepsRepeat

Page 21

283. Outdoor unit failure mode tableThe upper lamp of OPERATION INDICATOR lamp(Indoor unit) Abnormal point (Failure mode/protection) LED indication(Ou

Page 22

2911-3. TROUBLESHOOTING CHECK TABLENo. Symptom LED indication Abnormal point/ Condition Condition Remedy 1Outdoor unit does not op-erate. 1-time fl as

Page 23

3MUZ-HJ25VA -E1MUZ-HJ35VA -E1MUZ-HJ50VA -E1 1. New model1TECHNICAL CHANGESACCESSORIESAir outletDrain outletPipingDrain hoseAir inlet(Back and side)MU

Page 24 - ACTUATOR CONTROL

3011-4. TROUBLE CRITERION OF MAIN PARTSMUZ-HJ25VA MUZ-HJ35VA MUZ-HJ50VAPart name Check method and criterion FigureDefrost thermistor(RT61) Measure

Page 25 - TROUBLESHOOTING

3111-5. TROUBLESHOOTING FLOWAre the voltages balanced?Disconnect the connector (CN61) between compressor and the power module (IC700).Replace the inve

Page 26

32Refer to 11-5. “Check of compressor operation time”.Does the compressor operate continuously?Refer to 11-5. “Check of compressor start failure”.OK

Page 27 - Operational procedure

33 F Check of compressor start failureAfter the compressor is heated with a drier, does the compressor start? 1Replace the compressor.Compressor st

Page 28

34 H Check of R.V. coil First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4. In case CN721 is not conn

Page 29

35Check the resistance of fan motor. (Refer to 11-4.)Is the resistance of fan motor normal?Replace the outdoor fan motor.Disconnect the connector CN77

Page 30

36 K Check of LEV (Expansion valve)Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote con

Page 31 - B Check of open phase

37Check the outdoor fan motor. (Refer to 11-5. .)Is the fuse (F901) blown on the in-verter P.C. board?Check the connection of the connectors (CN931, C

Page 32 - C Check of compressor

38 M How to check miswiring and serial signal error1 Make sure that the wiring is correct. If the pro-cedure is performed without correcting miswir-i

Page 33

39 N Electromagnetic noise enters into TV sets or radiosYesIs the unit earthed?NoEarth the unit.YesIs the distance between the antennas and the indoo

Page 34 - H Check of R.V. coil

43SPECIFICATIONOutdoor model MUZ-HJ25VA MUZ-HJ35VAPower supply Single phase, 230 V, 50 HzCapacity Rated frequency (Min.-Max.)CoolingkW2.5 (1.3 - 3.0

Page 35 - MUZ-HJ25VA MUZ-HJ35VA

40-20 -10 0 10 20 30 400102030405060708090100Temperature (°C)Defrost thermistor (RT61)Temperature (°C)Discharge temperature thermistor (RT62)0 1020304

Page 36 - J Check of power supply

41-20 -10 0 10 20 30 400102030405060708090100Temperature( )Defrost thermistor(RT61)Outdoor heat exchanger temperature thermistor(RT68)Temperature(

Page 37

12-1. MUZ-HJ25VA MUZ-HJ35VANOTE: Turn OFF power supply before disassembly.OPERATING PROCEDURE PHOTOS1. Removing the cabinet and the panels(1) Remove

Page 38 - Figure 1

OPERATING PROCEDURE PHOTOS2. Removing the inverter assembly, inverter P.C. board(1) Remove the cabinet and the panels. (Refer to 1.)(2) Disconnect the

Page 39

OPERATING PROCEDURE PHOTOS4. Removing the discharge temperature thermistor and the defrost thermistor(1) Remove the cabinet and the panels. (Refer to

Page 40

12-2. MUZ-HJ50VANOTE: Turn OFF power supply before disassembly.OPERATING PROCEDURE PHOTOS1. Removing the cabinet and the panels(1) Remove the screw fi

Page 41

OPERATING PROCEDUREPHOTOS2. Removing the inverter assembly, inverter P.C. board(1) Remove the cabinet and the panels. (Refer to 1.)(2) Disconnect the

Page 42 - DISASSEMBLY INSTRUCTIONS

OPERATING PROCEDUREPHOTOS5. Removing the outdoor fan motor(1) Remove the cabinet and the panels. (Refer to 1.)(2) Disconnect the following connectors:

Page 43 - OPERATING PROCEDURE PHOTOS

© Copyright 2012 MITSUBISHI ELECTRIC CORPORATIONDistributed in Mar. 2013. No. OBH648 REVISED EDITION-ADistributed in Dec. 2012. No. OBH648Made in Ja

Page 44

5Outdoor model MUZ-HJ50VAPower supply Single phase, 230 V, 50 HzCapacity Rated frequency (Min.-Max.)CoolingkW5.0 (1.3 - 5.0)Heating 5.4 (1.4 - 6.5)B

Page 45 - 12-2. MUZ-HJ50VA

6Specifi cations and rated conditions of main electric partsModel Item MUZ-HJ25VA MUZ-HJ35VASmoothing capacitor (C61) 800 μF 420 V Diode module(DB61)

Page 46 - OPERATING PROCEDURE

790807060504030201063 125 250 500 1000 2000 4000 8000NC-60NC-50NC-40NC-30NC-20NC-70OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BARBAND CENTER

Page 47

8Unit : mmMUZ-HJ25VA MUZ-HJ35VA5OUTLINES AND DIMENSIONSREQUIRED SPACE100 mm or more350 mm or more200 mm or more100 mm or more100 mm or moreMUZ-HJ50VA

Page 48

9MUZ-HJ25VA 6WIRING DIAGRAMMUZ-HJ35VAOBH648A